Recommended Lighting Values Table

“Architectural Lighting Design Standards” GB50034-2013 Recommended Value Table

Application placesAverage illuminance value (Lux)
machiningroughing200 
General processing tolerance ≥0.1mm300 
General processing tolerance <0.1mm500 
Mechanical and electrical instrument assemblyLarge items200 
General parts300 
Precision500 
Extra precision750 
storehouseLarge parts warehouse (steel materials, large finished products, gas cylinders)50 
General parts100 
Precision parts library (such as tools, small parts)200 
substationPower distribution device library200 
Transformer room100 
General control room300 
IronmakingFurnace top platform, platforms on each floor30 
Casthouse, casthouse100 
Winch room, gas cleaning water distribution room50 
Steelmaking and continuous castingSteelmaking main workshop and platform150 
Continuous casting pouring platform and cutting area150 
Finishing cleaning line200 
thermal power plantThermal power plant boiler room100 
Generator room200 
main control room500 