Supplier to Saudi Aramco

HLDP11-Series Explosion-proof Electrical Apparatus (For Cable Connection)

  • Home
  • Product
  • HLDP11-Series Explosion-proof Electrical Apparatus (For Cable Connection)

HLDP11-Series Explosion-proof Electrical Apparatus (For Cable Connection)

  • Explosion protection

-IECEx(IEC)

-ATEX(CENELEC,EN)-China Ex(GB)

  • Application inhazardous area

-Zone 1 and Zone 2

-Zone 21 and Zone 22

  • Three types of explosion protection (Exdb IB,Ex dbIIB+H2,Ex tb IIIC)
  • Aluminum alloy enclosure,power coated.
  • Equipped with hinges and door handle,easy to installation and maintenance,also protectthe flameproofsurface from damage when the cover is opening or closing
  • Can becustomized upon request and able tomeet the usage restrictions of the certificate
  • Direction,size andquantity ofcable entry can be customized and meet the requirements of dissipated power and mechanical strength of the enclosure.

Nomenclature

Selection Table

Maximum quantity of terminals that can be installed are shown in the table below:

Ex marking Gas Ex II2 G Ex db IIB T6/T5/T4 Gb Ex db IIB T6/T5/T4 Gb Ex d IIB T6/T5/T4 Gb
Ex II2 G Ex db IIB+H2 T6/T5/T4 Gb Ex db IIB+H2 T6/T5/T4 Gb Ex d IIB+H2 T6/T5/T4 Gb
Dust Ex II2 D Ex tb IIIC T80/T95/T130℃Db Ex tb IIIC T80  T95/T130℃Db Ex tD A21 IP66 T8O/T95/T1307
Conformity to standards IEC 60079-0, IEC60079-1, IEC 60079-31
EN60079-0, ENA0079-1, EN 60079-31
GB3836.1, GB3836.2, GB12476.1, GB12476.5
Enclosure
material
Enclosure Aluminum alloy enclosure powder coated industrial gray with dark lines texture(RAL7035)
Exposed fastener Stainless steel
Components Brand of
terminal
International brand
Rated voltage Max.  1000V AC,1500V DC
Rated current Max.  1200A
Frequency 50Hz/60Hz
Maximum
dissipation
power
Enclosure
size
Type Ta:+60℃ Ta:+40℃ Weight of
empty
enclosure
T6/T80℃ T5/T95℃ T4/T130℃
Power Rated current Power Rated  current Power    Rated current
282X210X170 03 45W E63A 110W 110W 9.0kg
350×210×170 07 45W 63A~100A 80W 139W 11.5kg
350X300X235 08 45W 63A~100A 80W 139W 16.6kg
433X350X280 11 100W 100A ~250A 288W 288W 26kg
563X433X280 15 130W 250A ~400A 365W 400A ~800A 365W 800A~1200A 48kg
720X563X280 19 200W 250A~400A 448W 400A~800A 448W 800A~1200A 85kg
720×563X350 21 210W 250A ~400A 690W 400A ~B00A 690W 800A~1200A 95kg
Degree of protection 03.07.08.11.15–IP66/P67
19.21–IP66
Ambient temperature -20C~+4Q/60℃,-40=-+40/601
Cable entries Standard M×1.5(Upon request).NPT thread (Optional), HLB M- is recommended,refer to
Page D/11~D/20 for details.
Inlet direction Upon request
Installation
Method
Hanging type (Standard)
Floor type (Optional)