HLBX03- Series Explosion-proof Control Station

  • Explosion protection

-IEC Ex(IEC)

-ATEX(CENELEC,EN)

-China Ex(GB)

  • Application in hazardous area

-Zone 1 and Zone 2,

-Zone 21 andZone22

  • There are 5 typesof enclosures,assembled with explosion-proof components (control buttonsswitches,indicator lights,pot en ti o meters,ammeters,etc.)and terminal blocks.The components are rail-type structure,which can be quickly installed and convenient for installation and maintenance.
  • The emergency stopbutton can be equipped with anti-mi s operation mechanism and padlock by requirements
  • Stainlesssteel exposed fasteners,anti-drop structure,convenientfor installation and maintenance.

Nomenclature

Note:

1. Example: HLBX03-19A2B1GXM25X1.5, 19# enclosure, which with two control buttons, one ammeter; wall mounting type;one bottom inlet M25X1.5:

2. The specific requirements ofthe components are based on the drawings;

3. Button code, switch code, signal lamp code, ammeter code see P B/94;

4.The rain shade is customizable by requirements.

Components and accessories

Note:

1.HL0109-48 0ccupies 2 components position;

2.φ65 and square operating handle occupies 2 components position;

3.HL0153 switch,HL0109-72 occupies 2-3 components position.

Selection Table

Height of electrical accessories

Flectrical
accessories
Erame
of ammeter
Standard
button
Double
Button
Button
with key
Self-lock
button
Mushroom
button
Mushroom
button
with key
Indicator
light
illuminated
button
Control
switch
S1.S3
Control
switch
S2
Potentiometer
(single tum)
Potentiometer
mulit tum)
h(mm)1120.521.538(62)403245(69)23.520.540422740.5

Accessories list

Ex marking Gas Ex II2 G Ex db eb IIC T6 Gb Ex db eb IIC T6 Gb Ex de lIC T6 Gb
Dust Ex II2 D Ex tb IIIC T80℃ Db Ex tb IIIC T80℃ Db Ex tD A21 IP66 T80℃
Conformity to standards IEC 60079-0,IEC 60079-1,IEC 60079-7,IEC 60079-31
EN 60079-0,EN 60079-1,EN 60079-7,EN 60079-31
GB3836.1,GB3836.2,GB3836.3,GB12476.1,GB12476.5
Enclosure
materials
Enclosure GRP(Polyester resin,glass fibre reinforced),anti s t a t c
Rain shade B ended steel plate surface powder coated,industrial gr e y with dark lines texture (RAL7035)
or stainless steel 304/316,please note when needed.
Colo r of enclosure Black
Exposed fasteners Stainless steel exposed fasteners,anti-drop structure
Rated voltage Maximum 415VAC,250V DC
Rated current 6A、10A、16A
Wire diameter ≤6A:0.75~2.5mm²
6A<I≤10A:1.5~2.5mm²
10A<I≤16A:2.5mm²
Degree of protection IP66
Ambient temperature -40℃~+40/45/50/55/60/65/70℃
Components HL0101 explosion-proof control button,refer to P B/122 for technical parameters
HL0102 explosion-proof indicator,refer to P B/130 for technical parameters
HL0101-S explosion-proof control switch,refer to P B/126 for technical parameters
HL0109 explosion-proof ammeter,refer to PB/120 for technical parameters
Installation method Wall type and stand type
Cable entries Wall type M16X1.5~M63X1.5,G1/2~G2
Without cable entry device as default,please note if which is needed.
Stand type G1 only