Supplier to Saudi Aramco

HLBD56- Series Explosion-proof LED Lightings

  • Home
  • Product
  • HLBD56- Series Explosion-proof LED Lightings

HLBD56- Series Explosion-proof LED Lightings

  • Explosion protection

-China Ex(GB)

  • Applicationin hazardous area

-Zone 1 and Zone 2,Z

-one 21 and Zone 22

  • Light source and power:

-LED:10W,20W,30W,40W,50W,60W,70W,80W,100W,120W

  • Five enclosuretypes:20,40,60,70,120
  • Lightsource cavity,electrical cavityand wiring cavity are separately.Only need to open the wiring cavity when wiring,convenient and safe for installation and maintenance
  • Wireless connection between lamp bodyand installation accessories and installation accessories of various installation methods can beinterchangeable and universal.Installation and maintenance are convenient,fast and safe.
  • Emergency unit can be equipped upon request.
  • Protectivegrid can be equipped upon request.

Nomenclature

Luminous distribution curve

Selection Table

Flat glass typeConvex glass type
TypeWeight (kg)TypeWeight (kg)
HLBD56-20S1.15HLBD56-W20S1.73
HLBD56-20GS1.53HLBD56-W20GS2.11
HLBD56-20XS1.65HLBD56-W20XS2.23
HLBD56-20BS2.25HLBD56-W20BS2.83
HLBD56-402.6HLBD56-W403.64
HLBD56-40G2.98HLBD56-W40G4.02
HLBD56-40X3.1HLBD56-W40X4.15
HLBD56-40B3.7HLBD56-W40B4.75
HLBD56-603.52HLBD56-W604.1
HLBD56-60G3.9HLBD56-W60G4.47
HLBD56-60X4.05HLBD56-W60X4.97
HLBD56-60B4.62HLBD56-W60B4.21
HLBD56-703.87HLBD56-W704.95
HLBD56-70G4.25HLBD56-W70G5.32
HLBD56-70X4.37HLBD56-W70X5.45
HLBD56-70B4.97HLBD56-W70B6.05
HLBD56-1206.07HLBD56-W1206
HLBD56-120G6.45HLBD56-W120G6.37
HLBD56-120X6.57HLBD56-W120X6.5
HLBD56-120B7.18HLBD56-W120B7.1

Accessories list

ItemPicturePurchase codeWeight(kg)
HLBD56-20S Glass cover ring 4.02.211.00020.5
HLBD56-50 Glass cover ring4.02.205.00021.2
HLBD56-60 Glass cover ring4.02.211.00221.2
HLBD56-70 Glass cover ring4.02.211.00221.2
HLBD56-120 Glass cover ring4.02.211.00422
HLBD56-W20S Glass cover ring 4.02.211.00021
HLBD56-W50 Glass cover ring4.02.205.00021.3
HLBD56-W60 Glass cover ring4.02.211.00221.3
HLBD56-W70 Glass cover ring4.02.211.00221.3
HLBD56-W120 Glass cover ring4.02.211.00422.1
HLBD56-20S Protective grid 2.03.01000020.1
HLBD56-50 Protective grid2.03.01000120.2
HLBD56-60 Protective grid2.03.01000220.2
HLBD56-70 Protective grid2.03.01000220.2
HLBD56-120 Protective grid2.03.01000320.3
HLBD56-W20S Protective grid 2.03.52000410.2
HLBD56-W50 Protective grid2.03.01002320.2
HLBD56-W60 Protective grid2.03.01000520.3
HLBD56-W70 Protective grid2.03.01000520.3
HLBD56-W120 Protective grid2.03.01000620.5

Accessories list

The installation accessories required by different installation methods see the table below;

Installation methodItemQtyPurchase codeWeight(kg)
G-Pendant typeExplosion-proof pipe joint (G3/4 or M25X1.5)12.12.1100014(G3/4)
2.12.1100114(M25X1.5)
0.06
Straight pipe,both ends M25X1.5,length 300mm14.02.901.01130.34
Explosion-proof terminal box11.03.101.000010.66
Mounting bracket12.14.07110010.04
X-Ceiling typeOutlet box11.52.901.000820.9
X1-Ceiling typeOutlet box11.52.901.000621.2
B-Wall typeOutlet box11.52.901.000711.3
Mounting bracket12.14.07070510.68
B1/B2-Wall typeExplosion-proof terminal box11.03.101.000010.66
Mounting bracket12.14.07110010.04
30°/90°bending pipe11.02.901.00120(30)
1.02.901.00121(90°
30°:0.4,90°:0.55
Chain(length 300mm)12.15.10001010.1
Expansion hook12.18.20000110.02
Flower basket hook(galvanized)12.18.20000010.04
D1-Hanging chain
type(side opening)
Outlet box11.52.901.000811.3
Chain(length 300mm)12.15.10001010.1
Expansion hook12.18.20000110.02
Spring clasp12.18.16040910.003
Mounting bracket12.14.07070530.04
M8 Eye bolt12.18.11000210.04
D3-Hanging chain typeOutlet box11.02.901.000830.92
Chain (length 300mm)12.15.10001010.1
Expansion hook12.18.20000110.02
Spring clasp12.18.16040910.003
Mounting bracket12.14.07070530.06
M8 Eye bolt12.18.11000210.04
F1/F2-Flange typeFlange pole(G11/4)11.02.901.0009710.7
90°/25°Outlet box11.02.901.0009225°:1.08,90°:1.35
h1/h2-Fence typeFence pole11.02.901.000955.9
Explosion-proof pipe joint(G3/4 or M25X1.5)12.12.1100014(G3/4)
2.12.1100114(M25X1.5)
0.06
Explosion-proof terminal box11.03.101.000010.66
Note:The accessories that are not mentioned in the table,user need provide it by themself.

 

Ex marking
Gas
Ex d IIC T6 Gb
Dust
Ex tD A21 IP66 T80℃
Conformity to standards
GB3836.1,GB3836.2,GB12476.1,GB12476.5
Structure,
Material
Enclosure
Aluminum alloy enclosure,powder coated,industrial grey with dark lines texture(RAL7035)
Transparent cover
Tempered glass,resistant to 4J impact,W-type glass undergoes a special process,with
a larger irradiation angle,and better anti-glare effect
Protective grid
Steel wire powder coating (white)or stainless steel,please note when needed
LED power
Wide voltage input (90~305VAC),(10W type is 170~250VAC,can be customizd to AC/DC24V,AC/DC36V,20WS type is 90~250VAC),constant power output,powe factor≥0.95.With protection functions of constant current,over current,open circuit short circuit,surge prevention,etc.
Reflector
Secondary optical design,significantly improve the efficiency of the lamp,uniform illumination,no glare
Emergency unit
Explosion-proof emergency unit,when the power supply is off,the lamp will automatically switch to the emergency lighting state
Exposed fastener
Stainless steel
Light
Source
Specification
LED(Cree),multiple arrangement,luminous efficiency≥140 Im/W,color rendering ≥70
Power (W)
LED:10W,20W,30W,40W,50W,60W,70W,80W,100W,120W
LED (CCT)
color temperature
Cool white:5700K (default)Note:Warm white (3000K)and natural white (4000K)
can be customized,please note it when ordering.
Rated voltage
220,230,240V AC(10W type:customizable to 24/36VAC,24/36VDC)
Frequency
50/60Hz
Degree of protection
IP66
Ambient temperature
-20℃~+40℃
Terminal block
3X1.5~4mm²(L+N+PE)
Cable entries
1-G3/4(Pendant type)
2-G3/4(Wall type,pendant type with terminal box,hanging chain type,ceiling type)
4-G3/4(Ceiling type,optional)
Available cable outer diameter(mm)
φ10-φ14(mm)
Emergency
unit
technical
parameters
Emergency unit
Dedicated emergency controller and battery pack,with overcharge and over discharge protection functions
Emergency power(W)
10W,20W,30W,40W,50W,60W,70W,80W,100W,120W
Emergency starting time
0.3s
Charging time
24h
Emergency lighting time
10W~20W:90min,30W~100W:60/90min

 

Size(mm)
Power(W)
A
B
B1
φC
D
E
F
10,20S
181
152
170
135
265
189
285
20,30,40,50S
213
184
202
196(W:218)
297
221
270
5,060
221
192
210
240
305
229
270
70
226
197
215
240
310
234
275
80,100,120
236
207
225
292
317
241
288

With emergency unit

Power
Size(mm)
  10~50
  (W)
60~100
   (W)
N
225
228
P
187
214
Q
156X40
156X40