Supplier to Saudi Aramco

HL0153-Series Explosion-proof Switch Module

HL0153-Series Explosion-proof Switch Module

  • Explosionprotection

-IEC Ex(IEC)

-ATEX(CENELEC,EN)

-China Ex(GB)

  • Applicationin hazardousarea

-Zone1 and Zone 2

  • Customized engineering plastics enclosure,which has high strength andcorrosion resistance;
  • Theswitch module has anacceleration mechanism with spring energy storage and instantaneous release to realize rapid switching on or off;
  • Theswitch should be used in an increased-safety enclosure,and cannot be used alone in an explosive gas environment.

Nomenclature

Note: Switch module can be customized upon request.

Selection Table

Selection Table of Electrical accessory

Handle code    DescriptionApplicable
current range
(A)
Handle code    Description     Applicable
   current range
        (A)
S3301Standard type(Black)25、40、80S3303Standard type (Black) 25、40、80
S3302Emergency type (Red/Yellow)25,40,80S3304Emergency type (Red/Yellow) 25,40,80
S3201Standard type (Black) 180S3203Standard type (Black) 180
S3202Emergency type (Red/Yellow) 180S3204Emergency type (Red/Yellow) 180
For load isolating switchFor safety switch

Ex-marking Gas Ex II2 G Ex d e IIC Gb Ex d e IIC G b Ex d e IIC Gb
Conformity to standards    IEC 60079-0,IEC 60079-1,IEC 60079-7,IEC 60079-31
EN 60079-0,EN 60079-1,EN 60079-7,EN 60079-31
GB3836.1,GB3836.2,GB3836.3,GB12476.1,GB12476.5
Material Switch enclosure    GRP(Polyester resin,glass fibre reinforced)
Electrical accessory    Nylon(PA66)
Pole    2P,3P,4P,6P
Switch capacity (A)
AC-23
AC-3
AC-11
AC230V 25 40 80 180
AC400V 25 40 80 180
AC500y 20 40 80 150
AC690V 16 32 63 125
Terminal cross-sectional area(mm²) 2X1.5~4 2X10 2X16~25 2X50~95
Rated short-time tolerance current I cw(k A) 3 3 10 10
Rated short-circuit connection capacity I cm(k A) 4 4 17 17
Fuse short circuit protection 20kA 500V/35A(25A) 20kA 500V/63A(40A) 50kA 500V/160A(80A) 50kA 500V/250A(180A)
Rated insulation voltage U i(V)    800
Rated shock withstand voltage U imp(k V)    6
Fuse protection characteristics    g G
Ambient temperature    -40℃~+40/+55℃

  • Outline and installation Dimension of Moudle (Dimensions in mm)

      Size
(mm)
Pole
25A 40A 80A 180A
A B C D E F G A B C D E F G A B C D E F G A B C D E F G
3P 39 105 50 71 72 80 5.5 67 155 73 117 113 125 6.5 73 205 131 178 140 160 10 71 232 146 200 170 192 12
4P 39 105 67 155 73 205 71 232
3P+N 39 105 67 155 73 205 71 232
3P-IV 39 105 41 155 47 205 45 232
3P-1 21 105 41 155 47 205 45 232
4P-IV 21 105 41 155 47 205 45 232
4P-1 21 105 41 155 47 205 45 232
6P-1 37 140 43 185 40 245 39 285
6P-I 37 140 43 185 40 245 39 285

 

  • Outline and Installation Dimension of Electrical accessory(Dimensions in mm)

Related products

Request a Quote

Get professional explosion-proof product solutions to keep you safe!